USCG

USCG

USCG

Product catalog summary
Specifications:
Main and Backup Power Supply: 24 VDC (± 4)
Power Supply Protection: 5 Amp
Power Consumption: 0.5 Amp
Connection: 4 x 20 mm cable glands, Max Wire Size: 12 AWG (2.05 mm)
Dimensions: 255(w) x 180(h) x 61(d) mm / 10(w) x 7(h) x 2.4(d) in
Weight: 1 kg
Enclosure Materials: Polycarbonate Plastic
Product Overview:
The Sea-Fire Marine “FireStop” is a USCG approved conventional fire detection system designed for marine environments. It provides quick identification of fire alarms and events, featuring a weather-resistant monitoring system capable of detecting fire, heat, and smoke. This system is suitable for both commercial and recreational marine markets, offering an economical solution for fire detection.
Functions:
Fire and failure detection, including fault detection (open or short circuit).
Inputs/Outputs:
  • CAT5 port for communication with Display Panel (PN: 131-933) and Zone Identification Panel (ZIP) (PN: 131-529/548).
  • Display Panel and ZIP Push Button for Alarm Reset and Silencing.
  • NAC Alarm Output: 2 amp max.
  • Adapter Unit Reset Relay: 1 unit rated at 16 Amps.
System Capacity:
  • Standard 2 zone system (Accommodation and Engine Room).
  • Zone Capacity: 2 detectors and/or manual call points per zone.
  • Expandable to 4 zones per Adapter Unit and up to 16 zones per Zip Panel.
  • Compatible with Hochiki marine detectors and accessories.
Protection and Operating Requirements:
Ingress Protection: IP66
Operating Temperature: -25°C to 70°C (-13°F to 158°F)
Mounting: Surface Mount
Compliance:
Conforms to UL864 standards.
Contact Information:
Sea-Fire Marine, 9331-A Philadelphia Rd., Baltimore, MD 21237 USA
Phone: +1(410) 687-5500
Email: [email protected]
See more

Catalog excerpts

USCG-1

^^/^R^ULB FIRE SUPPRESSION TECHNOLOG YOUR ONBOARD SAFE CHOICE ™ ffmt*W■#f ^* FIRE DETECTION & ALARM - FIRESTOP Sea-Fire Marine "FireStop" is a USCG approved conventional fire detection system that provides quick and clear identification of fire alarms and The Fire Control Panel (FCP) features a weather resistant monitoring system with fire, heat and smoke monitoring capability. Designed for the increasing sophistication of modern vessels in the commercial and recreational marine market, this innovative accessory compliments Sea-Fire's fire suppression product offering to meet the aesthetic value of intuitive operation and increased safety The detection system is the ultimate economical choice for the commercial and recreational marine «BTOP FIRE CONTROL PANa DETECTION AND MONITORING SYSTEM Part Number 131-501 Fire Stop Fire Control Panel Electrical Specifications Mechanical Specifications

 Open the catalog to page 1
USCG-2

Zone Identification Panel PN: 131-529 Silence Enable Switch PN: 131-909 Display Panel PN: 131-933 Heat Detector PN: 130-821 Manual Pull Station PN: 131-923 Smoke Detector PN: 130-822 24VDC Main Supply 24VDC Backup Supply Functions Fire and failure detection: fault (open or short circuit). Environmental Protection Protection Level: Operating Requirements: • CAT5 port for receiving and sending signals to the Display Panel (PN: 131-933) and Zone Identification Panel (ZIP) (PN: 131-529 (gray) or 131-548 (black)). Surface Mount Conforms to UL864. • Display Panel and ZIP Push Button (Reset and Silencing...