Overview: The LONOX UCC (Ultra Clean Combustion) System by SAACKE is designed to meet stringent international NOX emission standards, such as the 2017 limit of 30 mg/m³ based on 3% dry O2 in Chinese urban areas. It achieves this without the need for additional measures or additives, thanks to its advanced burner technology.
Specifications:
  • Applications: Suitable for shell boilers and water-tube boilers with a capacity range of 10 - 80 t/h.
  • Burner Capacity: Maximum of 8 - 64 MW, with other sizes available upon request.
  • Fuels: Compatible with all standard gaseous fuels.
  • NOX Emissions: Less than 30 mg/m³, depending on boiler design.
  • Control Range: Up to 1:10, depending on burner size.
Design and Efficiency: The burner features a low-pressure resistance design in the windbox, aiding in energy savings. It is equipped with a single gas train and is adaptable to various boiler designs and fuel gas supply pressures. The burner draft loss is under 25 mbar, depending on design.
Product Features:
  • Extremely low NOX emissions without secondary measures.
  • Control range up to 1:10.
  • Excess air ratio under 15% at 100% MCR.
  • Suitable for short furnaces.
  • TÜV-certified emissions.
  • Reduced operating costs and maintenance time.
  • Conforms with European and Chinese guidelines.
Technical Data:
  • Burner Sizes: Available in sizes 80, 120/160, 320, and 640 with varying dimensions and capacities.
  • Operating Data: Maximum thermal capacity ranges from 8 MW to 64 MW, with corresponding boiler capacities from 10 t/h to 80 t/h.
  • Burner Weight: Ranges from 780 kg to 3,500 kg depending on size.
Applications: The system is applicable in various industries including energy and heat supply, chemical, refineries, food, building materials, steel and metal production, and waste incineration.
Contact Information: SAACKE GmbH, Südweststraße 13, 28237 Bremen, Germany. Tel: +49 421 6495-0, Fax: +49 421 6495-5224, Email: [email protected], Website: www.saacke.com
See more

Catalog excerpts

LONOX UCC-1

Technical data sheet LONOX UCC (Ultra Clean Combustion) System Energy and heat supply Chemical industry Refineries Food industry Building materials industry Steel and metal production Waste incineration And more … LONOX UCC (Ultra Clean Combustion) System The SAACKE LONOX UCC System complies with even the strictest The burner is designed for very low pressure resistance in the burn- international NO X Emission values, such as the 2017 limit values of er windbox, which is helpful for energy saving. It is equipped with 30 mg/m³ based on 3% dry O2 in Chinese urban areas. NO X reduction measures often lead to a high amount of excess O2 Suitable for different boiler design or a high level of CO. The reduction of these values often results in expensive and complex secondary measures or additional additives. The burner is suitable for different boiler design, different refrac- In contrast, the LONOX UCC System is based on SAACKE burner tory arrangement in firing chamber and different firing chamber technology that has proven its worth over decades. Thanks to a spe- geometry. Moreover the system is covered for different fuel gas cial, swirled flame geometry as well as a specially-engineered flame supply pressure. The burner draft loss of the combustion air is lower control, the burner avoids any necessary additional measures. This than 25 mbar (depending on the burner design). decreases fuel consumption as well as material costs and ensures compliance with emissions values, while maintaining a low flue gas recirculation rate of < 25%. Technical data: LONOX UCC System Applications Shell boilers and water-tube boilers in a capacity range of 10 - 80 t/h 8 - 64 MW (other sizes on request) All standard gaseous fuels < 30 mg/m³ (depends on boiler design) based on 3% O 2, dry Control range

 Open the catalog to page 1
LONOX UCC-2

(SAACKE) Burner dimensions LONOX 320/640 780 Product notes D E F* G H J K M O P ^1 Extremely low NOX emissions (< 30 mg/m3) based on 3% O2, dry ^ Control range up to 1:10** ^ Excess air ratio under 15% at 100% MCR ^ Also suitable for extremely short furnaces ^ TUV-certified emissions without secondary measures or additional additives ^1 Suitable for shell boilers and water-tube boilers ^1 Reduced operating costs due to high-efficiency combustion technology and low auxiliary power requirement ^ Less maintenance time and exceptionally long life ^ Conforms with European and Chinese guidelines SAACKE...

 Open the catalog to page 2

All SAACKE catalogs and brochures

  1. se@vis pro

    2  Pages

  2. se@vis eco

    2  Pages

  3. Coke Oven Gas

    2  Pages

  4. EGCS-HM

    2  Pages

  5. Spare parts

    2  Pages

  6. Boiler Repair

    2  Pages

  7. 03_PB_DDZ-M

    2  Pages

  8. 05_PB_SKV-A

    2  Pages

  9. FMB-VF-Lonox

    2  Pages

  10. 14_PB_FMB-VD

    2  Pages

  11. 19_PB_EME-VFT

    2  Pages

  12. 08_PB_CMB-VS

    2  Pages

Archived catalogs

  1. 09_PB_CMB-HF

    2  Pages

  2. 20_PB_FMW-VD

    2  Pages

  3. System_Progress

    32  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.