M-SKD11

M-SKD11

M-SKD11

Product catalog summary
Standard Design
  • Material: AISI 316
  • Interface for Water Supply: DN150 PN16 (standard), DN100 PN16 (option)
  • Foam Tank Capacity: 680l (standard), 1450l (option)
  • Design Pressure (Water): 16 bar
  • Foam Concentrate Refilling Pump: 0.7 l/stroke
  • Test Pressure: 24 bar
  • Insertion Rate: 1% and 3% with tolerances of 0% to +30%
  • Flow Capacity: DN150: 1850 - 8070 l/min, DN100: 240 - 3400 l/min
  • Flow Tolerance: Nominal value ±5%
  • Minimum Pressure Loss: 30% of inlet pressure
  • Footprint: Approximately 1165x1300 mm
  • Weight (Dry): 405 kg
General Description
The foam skid is a compact unit designed to inject foam concentrate into the fire water line near the nozzles using water energy. It is compatible with Matre pop-up nozzles and other applications.
Design Description
The system supports a 680l or 1450l tank and is calibrated for 1% or 3% foam insertion rates. Inductor capacity ranges from K=280 to 3050, using DN100 or DN150 inductor sizes.
System Description
Main components include a foam concentrate tank and an inductor. The inductor creates a vacuum to draw foam into the water flow at a calibrated rate, typically 1% or 3%, using 30% of the water pressure. An actuator valve controls system activation, and foam insertion can be disabled for testing. Control panels can be installed indoors or outdoors.
Main Components
  • Skid for deck installation
  • Ventilated tank with dip stick and drain valve (200l or 300l)
  • Manual pump for foam refilling
  • Strainer at water inlet
  • Actuator valve
  • Pressure indicators at inductor inlet and outlet
  • Inductor size DN100 or DN150
  • Ball valves for pump and foam insertion control
Testing and Certification
  • Leakage test (tank)
  • Pressure test (water line)
  • Performance test
  • Material certificates
  • Certificate of conformity
Note: System capacity may be less than skid capacity due to downstream flow resistance.
See more

Catalog excerpts

M-SKD11-1

MATRE MASKIN E-mail : [email protected] www.matre.no DATA SHEET FOAM SKID FOR POP-UP SYSTEM M-SKD11 STANDARD DESIGN Interface for water supply Foam tank (atmospheric) Design pressure (water) Foam concentrate refilling Test pressure Insertion rate Flow (a), 7 bar 1% insertion rate Flow tolerance Minimum pressure loss

 Open the catalog to page 1
M-SKD11-2

MATRE MASKIN' E-mail : [email protected] www.matre.no DATA SHEET FOAM SKID FOR POP-UP SYSTEM M-SKD11 GENERAL DESCRIPTION The system is a compact unit designed to insert an exact rate of foam concentrate directly to the fire water line close to the nozzles only using some of the energy in the water. Only to be hooked up to the water line and control signal from the control panel. Special designed for systems using Matre pop-up nozzles, but also suitable to be installed in other DESIGN DESCRIPTION The system can carry a 6801 or 14501 tank. Calibrated to 1% or 3% insertion rate. Inductor capacity...

 Open the catalog to page 2

All Matre Maskin AS catalogs and brochures

  1. POP-UP SYSTEM

    4  Pages

  2. M-SKD10

    2  Pages

  3. M-SKD20

    2  Pages

  4. M-SKD21

    2  Pages

  5. M-BP15

    2  Pages

  6. M-BP30

    2  Pages

  7. M-BP40

    2  Pages

  8. M-BP60

    2  Pages

  9. M-BWP60

    1  Page

  10. M-WP60

    1  Page

  11. M-TRT2-03163

    2  Pages

  12. TET4

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.