M-SKD10

M-SKD10

M-SKD10

Product catalog summary
Standard Design
The Foam Skid for Pop-Up System M-SKD10 is constructed from AISI 316 material. It features a water supply interface of DN100 PN16, with an optional DN150 PN16. The foam tank is available in 200l or 300l capacities. The design pressure for water is 16 bar, with a test pressure of 24 bar. The foam concentrate refilling pump operates at 0.7 l/stroke. Insertion rates are calibrated at 1% and 3%, with tolerances of 0% to +30%. Flow rates at 7 bar vary depending on the insertion rate and interface size, with a nominal flow tolerance of ±5% and a minimum pressure loss of 30% of inlet pressure. The skid has a footprint of approximately 750x1000 mm and a dry weight of 260 kg.
General Description
This compact unit is designed to insert foam concentrate into the fire water line near the nozzles, utilizing water energy. It is compatible with Matre pop-up nozzles and other applications. The system requires connection to the water line and a control signal from the control panel.
Design Description
The system supports a 200l or 300l tank and is calibrated for 1% or 3% insertion rates. Inductor capacity ranges from K=280 to K=3050, using DN100 or DN150 inductor sizes.
System Description
Main components include a foam concentrate tank and an inductor. The inductor creates a vacuum to draw foam into the water flow at a calibrated rate, typically 1% or 3%, using 30% of the water pressure. An actuator valve controls system activation, and foam insertion can be disabled for testing. Control panels can be installed indoors or outdoors.
Main Components
  • Skid for deck installation.
  • Ventilated foam concentrate tank with dip stick and drain valve (200l or 300l).
  • Manual pump for foam refilling.
  • Strainer at water inlet to prevent nozzle clogging.
  • Actuator valve for system control.
  • Pressure indicators at inductor inlet and outlet.
  • Inductor size DN100 or DN150, calibrated for flow and insertion rate.
  • Ball valves for pump and foam insertion control.
Testing and Certification
  • Leakage test for the tank.
  • Pressure test for the water line.
  • Performance test.
  • Material certificates.
  • Certificate of conformity.
Note: System capacity for a pop-up system may be less than skid capacity due to flow resistance in downstream piping.
See more

Catalog excerpts

M-SKD10-1

E-mail : company®matre.no www.matre.no DATA SHEET FOAM SKID FOR POP-UP SYSTEM M-SKD10 STANDARD DESIGN Interface for water supply Foam tank (atmospheric) Design pressure (water) 16 bar Foam concentrate refilling 0,7 1/stroke Test pressure Insertion rate Flow (2) 7 bar 1% insertion rate using 1 y2" foam inlet. Flow tolerance Minimum pressure loss

 Open the catalog to page 1
M-SKD10-2

MATRE MASKIN' E-mail : [email protected] www.matre.no DATA SHEET FOAM SKID FOR POP-UP SYSTEM M-SKD10 GENERAL DESCRIPTION The system is a compact unit designed to insert an exact rate of foam concentrate directly to the fire water line close to the nozzles only using some of the energy in the water. Only to be hooked up to the water line and control signal from the control panel. Special designed for systems using Matre pop-up nozzles, but also suitable to be installed in other DESIGN DESCRIPTION The system can carry a 2001 or 3001 tank. Calibrated to 1% or 3% insertion rate. Inductor capacity...

 Open the catalog to page 2

All Matre Maskin AS catalogs and brochures

  1. POP-UP SYSTEM

    4  Pages

  2. M-SKD11

    2  Pages

  3. M-SKD20

    2  Pages

  4. M-SKD21

    2  Pages

  5. M-BP15

    2  Pages

  6. M-BP30

    2  Pages

  7. M-BP40

    2  Pages

  8. M-BP60

    2  Pages

  9. M-BWP60

    1  Page

  10. M-WP60

    1  Page

  11. M-TRT2-03163

    2  Pages

  12. TET4

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.