Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 1

Model YST Steam-Turbine Drive Centrifugal Liquid Chillers

Open the catalog to page 1
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 2

nomenclature The model number denotes the following characteristics of the unit: YST Chiller Model Special (Mandatory) Evaporator Code Condenser Code Compressor Code Design Level Steam Condenser Model Turbine Expansion Ratio No. of Turbine Nozzles Steam Turbine Base Model JOHNSON CONTROLS

Open the catalog to page 2
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 3

Introduction The YORK YST MaxE™ Chillers offer a complete combination of features for total owner satisfaction. MATCHED COMPONENTS MAXIMIZE EFFICIENCY Overall chiller efficiency cannot be determined by analyzing the theoretical efficiency of any one chiller component. It requires a specific combination of heat exchanger, compressor, steam turbine and steam condenser performance to achieve the lowest system steam rate. YORK YST MaxE chiller technology matches chiller system components to provide maximum chiller efficiency under actual - not just theoretical - operating conditions. REAL-WORLD...

Open the catalog to page 3
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 4

Introduction - continued PRECISION CONTROL OF COMPRESSOR OIL PRESSURE Utilizing our expertise in variable speed drive technology and applications, Johnson Controls has moved beyond the fixed head and bypass approach of oil pressure control. The old approach only assures oil pressure at the outlet of the pump rather than at the compressor, and allows no adjusteament during chiller operation. The YST MaxE chillers feature a variable speed drive oil pump, monitoring and providing the right amount of oil flow to the compressor on a continuous basis. This design also provides sophisticated...

Open the catalog to page 4
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 5

Ratings COMPUTERIZED PERFORMANCE RATINGS Each chiller is custom-matched to meet the individual building load and energy requirements. A large number of standard heat exchangers and pass arrangements are available to provide the best possible match. It is not practical to provide tabulated performance for each combination, as the energy requirements at both full and part load vary significantly with each heat exchanger and pass arrangement. Computerized ratings are available through each Johnson Controls sales office. These ratings can be tailored to specific job requirements. OFF-DESIGN...

Open the catalog to page 5
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 6

Optiview Control Center YST OPTIVIEW CONTROL CENTER The YORK OptiView Control Center, furnished as standard on each chiller, provides the ultimate in efficiency, automation, monitoring, data recording, chiller protection and operating ease. The Control Center is a factory-mounted, wired and tested state-of-the-art microprocessor based control system for R134a centrifugal chillers. The panel is configured with a 10.4" diagonal color Liquid Crystal Display (LCD) surrounded by “soft” keys, which are redefined with one keystroke based on the screen displayed at that time. This revolutionary...

Open the catalog to page 6
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 7

Equipment Specifications GENERAL The YORK YST MaxE Centrifugal Liquid Chillers are completely factory-packaged including the evaporator, refrigerant condenser, compressor, steam turbine, lubrication systems, power panel, control center, and all interconnecting unit piping and wiring. The steam condenser package is shipped separately. It is suitable for direct mounting onto the chiller or mounting along-side. The initial charge of refrigerant and oil is supplied for each chiller. When the optional refrigerant-condenser isolation valves are ordered, the unit may ship fully charged with...

Open the catalog to page 7
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 8

Equipment Specifications - continued The turbine casing is horizontally split. It is designed to allow longitudinal thermal expansion without the affecting alignment or efficiency of the turbine. The shaft and wheels are alloy steel with the wheels shrunk and keyed to the shaft. The turbine blades are 403 grade stainless steel and the shaft is ground throughout with stainless steel sprayed in the carbon ring end gland contact area. Stainless steel steam nozzles are furnished throughout the turbine. Carbon ring-end gland and diaphragm seals are furnished. The turbine-end gland carbon-ring...

Open the catalog to page 8
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 9

HEAT EXCHANGERS Shells Evaporator, refrigerant condenser and steam condenser shells are fabricated from rolled carbon steel plates with fusion welded seams. Carbon steel tube sheets, drilled and reamed to accommodate the tubes, are welded to the end of each shell. Intermediate tube supports are fabricated from carbon steel plates, drilled and reamed to eliminate sharp edges. The refrigerant side of each shell is designed, tested, and stamped in accordance with ASME Boiler and Pressure Vessel Code, Section VIII - Division I, or other pressure vessel code as appropriate. The steam side of the...

Open the catalog to page 9
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 10

Equipment Specifications - continued General The chiller is controlled by a stand-alone microprocessor based control center. The chiller control panel provides control of entire system, including turbine and steam condenser operation and monitoring. The control panel includes a 10.4". diagonal color liquid crystal display (LCD) surrounded by “soft” keys which are redefined based on the screen displayed at that time. The display is mounted in the middle of a keypad interface and protected by a locked enclosure. The screen details all operations and parameters, using a graphical...

Open the catalog to page 10
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 11

Safety shutdowns (will prevent unit from starting or operating) • Evaporator - low pressure • Evaporator - low temperature (Smart Freeze Point Protection) • Evaporator - transducer or leaving liquid probe failure • Evaporator - transducer or temperature sensor failure • Refrigerant condenser - high pressure contacts open • Refrigerant condenser - high pressure • Refrigerant condenser - pressure transducer out-ofrange • Compressor discharge - high temperature • Compressor discharge - low temperature • Compressor oil -high temperature • Compressor oil - low differential temperature •...

Open the catalog to page 11
Model YST Steam-Turbine Drive Centrifugal Liquid Chillers Design Level F - 12

Accessories and Modifications FLOOR MOUNTED STEAM CONDENSER As an alternative to the standard packaged location, the steam condenser package can be ordered for floor mounting adjacent to the chiller package. Prefabricated piping kits for the steam trunk, water piping and wiring between chiller package and steam condenser are not included with a floor mounted arrangement. These interconnecting components must be designed, supplied and installed by customer. Note: Interconnecting components may be ordered through the factory via a special quote upon request (site arrangement details will be...

Open the catalog to page 12