Overview: The document provides detailed information on various types of unit heaters offered by Heinen & Hopman, designed for heating large spaces such as workshops and engine rooms. The heaters utilize different heating mediums including electricity, hot water, steam, and thermal oil.
Types of Heating Units:
  • Electrical Heating Unit: VLE units are suitable for environments without boiler water, available from 3 kW to 36 kW.
  • Explosion-proof Electrical Heating Unit: FE2 units are ATEX certified for hazardous areas, available from 2.5 kW to 23.1 kW.
  • Hot-water Heating Unit: TGA units use boiler water or steam, available from 8.1 kW to 100 kW.
  • Thermal-oil Heating Unit: Suitable for extremely low temperatures, using thermal oil as the medium.
  • Portable Heating Unit: Delta units are movable and can be wall-mounted, available from 3 kW to 21 kW.
VLE Unit Heaters: Designed for rough environments, available in three types (VLE-4, VLE-5, VLE-6) with power ranging from 1.2 kW to 150 kW. They feature a built-in thermostat and thermal fuse for safety.
FE2 Unit Heaters: CE-marked and ATEX-approved for hazardous areas, featuring a Vacucore for efficient heat distribution. Available in various voltages and wattages.
Hot-water Unit Heaters: TGA heaters are designed for large rooms, using boiler water or steam. They come with options for different motor speeds and mounting kits.
Contact Information: The document lists contact details for Heinen & Hopman offices worldwide, including locations in Brazil, France, Germany, India, Italy, Netherlands, Norway, China, Poland, Romania, Russia, Singapore, South Korea, Spain, Sweden, Turkey, UAE, and the USA.
See more

Catalog excerpts

Unit heaters-1

Unit heaters PROVIDED BY HEINEN & HOPMAN

 Open the catalog to page 1
Unit heaters-2

Unit heaters The unit heaters are primary used to heat large spaces outside the accommodation like workshops, engine room, etc. The heating is done by hot-air supply through a heating coil. There are different types of heating units: Electrical heating unit: VLE heating units are mainly used in rough environments where boiler water is not available. The heating units are available from 3 kW to 36 kW. Explosion-proof electrical heating unit: FE2 heating units are ATEX certified unit heaters, specially developed for Ex II and EX IIB zone. The heating units are available from 2.5 kW to 23.1 kW. Hot-water...

 Open the catalog to page 2
Unit heaters-3

The VLE electrical fan heaters are designed for rough environments e.g. on ships, offshore, in workshops and large production areas. The heaters are available in three standard types: VLE-4, VLE-5 and VLE-6. The heaters are available in galvanized steel, but can also be supplied in different materials (on customer request). The heaters have a built-in thermostat (0-40 °C) which ensures optimal operation and minimizes the energy consumption. The heaters have a thermal fuse that turns off the heater at 110 °C. Heating element The heaters have an electric tube heating element made of stainless steel...

 Open the catalog to page 3
Unit heaters-4

FE2 unit heaters FE2 electrical fan heaters are CE-marked & ATEX-approved for use in hazardous areas. The heaters are designed for locations where specific explosive gases or dust may be present. The heaters use the Vacucore. The induced vacuum within the sealed core provides greater efficiency, distribution of heat across the face of the exchanger and a faster warm-up. If necessary, the entire core can be safely and easily replaced with a new exchanger or core. The heaters are ATEX Approved (directive 94/9/EC) and Ex II 2 G, Ex d IIB T3 Gb-certified. Heating element The heater core assembly...

 Open the catalog to page 4
Unit heaters-5

Alternatives available on request. Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

 Open the catalog to page 5
Unit heaters-6

Hot-water unit heaters Hot-water unit heaters are primarily designed for heating of large rooms, workshops or production areas. The TGA 2000 heaters are designed for onshore and offshore objects. The heaters are manufactured in different sizes, with a heating capacity from 8.1 kW to 100 kW and an air flow from 1430 m3/h to 9370 m3/h. Heating element The heaters use the boiler water as heating medium. The air will flow through the heating coil by using a axial or centrifugal fan. The heaters are available with copper tube and aluminum fins, but can also be supplied with stainless-steel casing...

 Open the catalog to page 6
Unit heaters-8

uAE (Dubai) T: +971 4263 5453 E: [email protected] usA - Fort Lauderdale, Florida T: +195 4463 0110 E: [email protected] usA - Houma, Louisiana T: +198 5876 7989 E: [email protected] Heinen & Hopman encourages a more sustainable world. By providing eco-friendly solutions and services we offer our clients the option of reducing energy consumption and thus co2 emissions. Visit greenmanifest.info for more information. HEINEN & HOPMAN

 Open the catalog to page 8