LPG regulators
88Pages

{{requestButtons}}

Catalog excerpts

LPG regulators - 2

Picture price lists 2009 GOK offers again a complete range of products used between the tank and the consumer appliance if liquid and gaseous energy is concerned. In the Picture Price Lists 2009 we have put new emphasis on the successful development of markets that become more and more difficult: • The clearly extended business area of tank data management that also allows solutions for complex monitoring duties, e.g. in industrial applications. • A wide range of fittings for oil firing installations that is now already suitable for use with biogenous components. • The comprehensive product...

Open the catalog to page 2
LPG regulators - 3

Table of contents Fields of application LPG Double stage tank regulator 2-stage regulator plant Regulator for industrial applications Accessories for tank plant Small cylinder plant Large cylinder plant Accessories for cylinder plant Pipe system Test equipment, accessories Description of the safety levels Description of the safety devices Abbreviations and units Description of the inlet and outlet connectors Article list (in ascending order by part number) Index Detailed description of the following topics: Safety levels: Our regulators are equipped with various safety devices. To allow you...

Open the catalog to page 3
LPG regulators - 4

Fields of application LPG Double stage tank regulator Double stage tank regulator low pressure 50 mbar with main shut-off valve, for outdoor installation “f“ or indoor installation “t“ from page 2-stage regulator plant 1st stage regulator with main shut-off valve and 2nd stage regulator for outdoor installation “f“ from page Regulator for industrial applications Pressure regulator for commercial and industrial use

Open the catalog to page 4
LPG regulators - 5

Fields of application LPG Small cylinder plant Low pressure regulator for small cylinder plants for private and commercial use Large cylinder plant Large cylinder regulator for one cylinder plants or with changeover / sequence valve for multiple cylinder plants for private and commercial use

Open the catalog to page 5
LPG regulators - 6

Double stage tank regulator The double stage tank regulator is an uncomplicated and inexpensive solution for installing a regulator system. By combining a medium and low pressure regulator directly on the gas withdrawal valve in the tank, the tank pressure is kept constant on the operating pressure on the gas consumer device. The double stage tank regulator can always be used if the pipeline between the tank and the consumer is not too long. The double stage tank regulators are supplied in various safety levels. That makes it possible to always choose the ideal combination of cost...

Open the catalog to page 6
LPG regulators - 7

Double stage tank regulator Double stage tank regulator PS 16 bar Straight-way form for direct connection to LPG tank Comprising: 1st stage regulator with safety pressure relief valve PRV and 2nd stage low pressure regulator mounted in one unit Advantages and equipment • POL connector, mounting bolts and diverse interior parts made of stainless steel Approval • EC type test according to Pressure Equipment Directive (PED) Technical data • Inlet pressure: 1.0 to 16.0 bar Note Detailed description of the safety equipment and the safety level, see page 65 onwards! Double stage tank regulator...

Open the catalog to page 7
LPG regulators - 8

Double stage tank regulator Double stage tank regulator type 052 PS 25 bar Straight-way form for direct connection to LPG tank Comprising: 1st stage regulator with safety overpressure shut-off valve OPSO and safety pressure relief valve PRV and 2nd stage low pressure regulator mounted in one unit Advantages and equipment • Lower installation height and length through lateral layout of the 1st stage that means there is more clearance to the tank upper edge • POL connector, mounting bolts and diverse interior parts made of stainless steel • Height-adjustable support also for inclination •...

Open the catalog to page 8
LPG regulators - 10

The 2-stage regulator plant comprises two pressure regulators that are installed in the pipeline separate from each other. The tank pressure is kept constant at an average pressure of 0.7–4.0 bar by using a 1st stage regulator. That means pressure losses in long pipelines do not make a big difference. The second pressure regulator is designed as a low pressure regulator and constantly regulates the operating pressure of the consumer device. The low pressure regulator is installed near the consumer device, outside or inside the building. The 2-stage regulator plants are supplied in various...

Open the catalog to page 10
LPG regulators - 11

2-stage regulator plant 1st stage regulator PS 16 bar For direct connection to LPG tank for plants with low pressure regulator before the house lead-in Comprising: 1st stage regulator Advantages and equipment • POL connector, mounting bolts and diverse interior parts made of stainless steel Technical data • Inlet pressure: 3.0 to 16.0 bar 1st stage regulator type 61F4B Without manometer POL x G 3/8 F 1.5 bar With manometer Ital. x G 3/8 F 1 stage regulator type 01266 Without manometer Version for use in Poland POL x G 3/4 M 1.5 bar st For direct connection to LPG tank for plants with low...

Open the catalog to page 11
LPG regulators - 12

2-stage regulator plant 1st stage regulator PS 25 bar For direct connection to LPG tank for plants with low pressure regulator before the house lead-in Comprising: 1st stage regulator with safety overpressure shut-off valve OPSO and safety pressure relief valve PRV Advantages and equipment • Short length in the version with integrated safety overpressure shut-off valve OPSO • POL connector, mounting bolts and diverse interior parts made of stainless steel • Height-adjustable support also for inclination • Emergency supply connector G 3/8 lh male thread with non-return valve • Insect...

Open the catalog to page 12
LPG regulators - 13

2-stage regulator plant Low pressure regulator For installation in LPG plants for commercial and industrial applications Comprising: low pressure regulator 2nd stage with safety pressure relief valve PRV Approval • EC type test according to Pressure Equipment Directive (PED) Technical data • Inlet pressure: 0.5 to 2.5 bar, except: • Connection for vent pipe G 1/8 F Note Use regulators without overpressure protection OPSO only if the nominal pressure of the consumer device corresponds to at least the protection pressure of the tank regulator! Detailed description of the safety equipment and...

Open the catalog to page 13