Catalog excerpts
FIRE SUPPRESSION & DETECTION SYSTEMS LUtifftf Inspected Vessels USCG/ABS Approved Marine & Offshore Yachts & Ships
Open the catalog to page 1WHY CHANGE from CO2 to Clean Agent Shipboard Fires Are Major Threats To Safety Of all the perils at sea, one of the most dangerous is fire. Difficult to deal with and potentially deadly, fire leaves the crew and passengers caught between two unforgiving elements. There’s no local fire department to call, it’s up to the crew to control the fire. Fire-fighting at sea and on water is especially demand- ing. The complexity of design and component requirement of a traditional marine CO2 system is there to achieve system safety, however, the results of an accidental discharge can be catastrophic....
Open the catalog to page 2Agent Halon 1301 Carbon Dioxide FE-13 FM-200® Novec™ 1230 Inergen Water Mist Typical ‘Marine’ CO2 System This table shows the typical usage of cylinders and chemical for a 500m3 system. While there is comparable weight of the Chemical Agent between CO2 and the Clean Agents, the number of cylinders required to store the chemical agent is reduced by a factor of 8:1, thereby giving a 40% reduction in system weight. Remote Manual Release Pneumatic Siren Pressure Switch Pneumatic Time Delay Today’s modern ‘Clean Agents’ are approved worldwide for use in ‘Occupied’ spaces, however even with these...
Open the catalog to page 3CLEAN AGENTS Remove Heat Energy, Not Oxygen Every second counts when a fire occurs on-board. Clean Agent systems reach extinguishing levels in less than 10 seconds. Since even a few seconds can mean the dif- ference between survival and a life destroying catastrophic fire, changing to the Fireboy FES system could give you a crucial margin of safety. That’s why you need a fast, people- safe and effective fire suppressant: Clean Agent Waterless Fire Protection from Fireboy-Xintex. Perfect For New Builds and Refits Manual Pull Box The ‘Fireboy’ FES System provides the perfect choice for both...
Open the catalog to page 4CLEAN AGENTS are approved by ALL Notified Bodies GL HFC-227ea/FM-200® FM-200® was originally developed to replace ozone-depleting fire suppressants such as halon 1301. FM-200® does not deplete stratospheric ozone. It has been proven safe for people through extensive pharmacological testing rivalled by no other fire suppressant. Many fire suppressants cause collateral damage to the equipment and the assets they were supposed to protect. But not FM-200®. It deploys quickly and cleanly without leaving any residue or causing collateral damage. FM-200® is the world’s most trusted choice in...
Open the catalog to page 5FIRE SUPPRESSION Fireboy Xintex FES Engineered System Fireboy-Xintex FES Systems are designed based on the requirements of: USCG, MSC Circular 848/1267, and NFPA 2001. Fireboy-Xintex Clean Agent Systems consist of DOT approved steel cylinder(s) equipped with a brass valve and internal siphon tube, and filled with HFC-227ea (FM-200) Extinguishant, then super-pressurized to 360 PSI at 70ºF. Multiple cylinders may be manifolded together in identical size and fill density to achieve coverage for the protected space. An embossed nameplate is perma- nently attached to the manufactured cylinder...
Open the catalog to page 6Fireboy-Xintex will provide design assistance to provide the best solution to your Clean Agent Fire Suppression requirements. Our extensive Fire Extinguisher Engineering and Manufacturing expertise covers 5 decades in the Marine Industry with the acknowledgement of Fireboy as innovators and supplier of top quality marine safety products. Our sys- tems are in use on Commercial, Military, Yachts, Cruisers, and boats of all sizes and styles. When it comes to reliability, no one else has earned the high level of trust that we have. der 6000 cubic feet, may be installed without time delays and...
Open the catalog to page 7FIRE SUPPRESSION -Fireboy Xintex FES Engineered System SHIP HAZARDS Fireboy-Xintex Systems have been used for suppressing fires in several locations on a ship. Typical shipboard hazard locations include but are not limited to: Engine Rooms Machinery Spaces Flammable Liquids Storage Paint Lockers Generator Rooms Electrical Control Rooms Pump Rooms Galley Design concentrations will vary based on the specific hazard being protected. Our design team will calculate the exact quantity of clean agent HFC-227ea ex- tinguishant required to meet the specific agent requirement. The FES System is...
Open the catalog to page 8FIRE DETECTION Fireboy Xintex Marine Safety System MARINE & OFFSHORE Analog Addressable Fire Alarm Control Fire Alarm Control Panel Model: Elite RSM Host up to 126 Apollo fire detection devices per loop. Fireboy-Xintex Elite RSM uses leading edge microprocessor technology to provide a flexible control system with high reliability and integrity. Designed for all small to medium sized vessels, Elite RSM control panels can be expanded and networked to handle 16 independent loops. With it’s large graphical display, ergonomic button, and indicator layout, the Fireboy-Xintex control panel is...
Open the catalog to page 9FIRE DETECTION Fireboy Xintex Marine Safety System TECHNICAL Panel Dimensions 14.5”w x 18.9”h x 4.25”d Weight 20 lbs (without batteries) Construction 16 AWG steel Enclosure Finish BS 00 A 05 light grey textured Mains Voltage Supply 110 VAC 60 Hz Display 8 lines of 40 characters graphic LCD Power Supply DC Rating 24 V 5.25 Amps USCG Approved Analogue Addressable Devices - Smoke - Heat - Heat/Smoke - Manual Pull Stations - Sounder Bases - Sounder Beacon Bases - Relay Bases - Beacons - Sounders - Intrinsically Safe Devices - Line Monitors The manufacturer reserves the right to amend...
Open the catalog to page 10REPEATER PANELS The Elite RSM fire alarm annunciator provides a simple and convenient method of extending the controls and indications of the Elite RSM fire alarm control panel to other locations. The large, graphic liquid crystal display and high brightness LED indicators duplicate the indications on the Elite fire alarm control panel at up to 15 additional locations via a simple, two-wire serial data connection. The Elite RSM is available in either a 24V DC powered option (which can be powered via an additional 2 cores from the Elite RSM control panel/local 24V DC supply) or a 110V...
Open the catalog to page 11All Fireboy - Xintex catalogs and brochures
-
Deckhead Mounting Box
1 Pages
-
Sounder Beacon Base
1 Pages
-
Relay Output Module
1 Pages
-
Elite RSM Fire Alarm Control
2 Pages
-
Methane Detectors
4 Pages
-
Elite Networking
2 Pages
-
Sounder Control Module
1 Pages
-
Low Power Relay Base
1 Pages
-
Isolating Base
1 Pages
-
4? Mounting Base
1 Pages
-
Mini Monitor Module
1 Pages
-
Isolator
1 Pages
-
Discovery Heat Detector
2 Pages
-
12 Ah Battery
2 Pages
-
Multi Flex Sounder Base
2 Pages
-
Multi-Tone Strobe
3 Pages
-
Wall Mount Horn/Strobe
4 Pages
-
Fire Suppression & Detection
13 Pages
-
fire alarm
2 Pages
-
propaneSystems
4 Pages
-
MONITOR UP TO 16 ZONES
1 Pages
-
Elite RS-M
2 Pages
-
FIRE DETECTION SYSTEM
1 Pages
Archived catalogs
-
MethaneFumeDetector.pdf
1 Pages
-
Carbon monoxide detector
12 Pages
-
GA Series
2 Pages