GHL 140-12

GHL 140-12

GHL 140-12

Product catalog summary
Specifications
The GEL Sealed VRLA Battery has a nominal voltage of 12V and a nominal capacity of 140AH. Its dimensions are 341mm (L) x 172mm (W) x 281mm (H) with a total height of 287mm. The battery weighs approximately 43kg and can handle a maximum discharge current of 1,350A for 5 seconds. It has an internal resistance of approximately 4.6 mΩ and uses M8 standard terminals. The container material is ABS with a UL94-V0 rating.

Constant-Voltage Charge
For cycle applications, the battery should have an initial current limit of less than 27.0A. Charging should continue until the battery voltage reaches 14.1V to 14.4V at 25ºC (77ºF). The voltage should be maintained until the current drops below 0.81A for at least 3 hours. The temperature compensation coefficient for charging voltage is -30mV/ºC. For standby service, the battery should be held across a constant voltage source of 13.6 to 13.8 volts with a current limit of 27.0A continuously. The temperature compensation coefficient here is -18mV/ºC.

Operating Conditions
The nominal operating temperature range is 25±3°C (77±5°F), with a wide operating temperature range from -20ºC to 55ºC. It is important to charge the battery within 6 months of storage to prevent permanent capacity loss due to sulfation.

Performance Characteristics
The battery's capacity is affected by temperature, with 103% capacity at 40°C (104°F), 100% at 25°C (77°F), and 86% at 0°C (32°F). The cycle life is related to the depth of discharge, and the battery's float life is influenced by temperature.

Discharge Characteristics
The document provides detailed tables for constant current and constant power discharge at various end voltages and time intervals, highlighting the battery's performance under different conditions.
See more

Catalog excerpts

GHL 140-12-1

GHL SERIESGEL BATTERIES GEL SEALED VRLA BATTERY LONG LIFE 12 YEARS OF EXPECTED LIFETIME Nominal Operating Temp. Range Cycle Application 1. Limit initial current less than 27.0A. 2. Charge until battery voltage (under charge) reaches 14.1V to 14.4V at 25°C(77°F). 3. Hold at 14.1V to 14.4V until current drop to under 0.81A for at least 3 hours. 4. Temperature compensation coefficient of charging voltage is -30mV/°C. Standby Service 1. Hold battery across constant voltage source of 13.6 to 13.8 volts with current limit 27.0A continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charge status. 2. Temperature compensation coefficient of charging voltage is -18mV/°C. Operating Temperature Wide operating temperature range from -20°C~55°C NOTE : The battery should be charged within 6 months of storage, Otherwise, permanent loss of capacity might occur as a result of sulfation

 Open the catalog to page 1
GHL 140-12-2

Discharging Time CHARGE CHARACTERISTICS (25°C/77°F)CYCLE LIFE IN RELATION TO DEPTH OF DISCHARGE ENERPOWER S.R.L. UFFICI e DEPOSITO: Via Boccioni, 7 - 20900 MONZA (MB) Tel. + 39 (039)-832152 Fax +39 (039)-2230441 E-mail : [email protected] - https://www.enerpowersrl.com

 Open the catalog to page 2

All ENERPOWER S.R.L. catalogs and brochures

  1. SLC 33-12

    2  Pages

  2. SLC 26-12H

    2  Pages

  3. SLC 26-12

    2  Pages

  4. SLC 18-12

    2  Pages

  5. SLC 12-12

    2  Pages

  6. SLC 9-12H

    2  Pages

  7. SLC 9-12

    2  Pages

  8. SLC 7,2-12

    2  Pages

  9. SLC 7-12

    2  Pages

  10. SLC 5-12

    2  Pages

  11. SLC 3.6-12

    2  Pages

  12. SLC 2,3-12

    2  Pages

  13. SLC 1,2-12

    2  Pages

  14. SLC 4.5-6

    2  Pages

  15. GHL 200-12

    2  Pages

  16. GHL 120-12

    2  Pages

  17. GHL 100-12S

    2  Pages

  18. GHL 75-12

    2  Pages

  19. GHL 55-12

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.