Overview: The CRM range of thyristor-controlled battery chargers is designed for versatility and reliability, suitable for various battery technologies including lead and nickel-cadmium. These chargers are compact, lightweight, and applicable in diverse sectors such as marine, military, and industry.
Specifications:
  • Input: 230 VAC or 400 VAC ± 10%, single-phase, 50 to 60 Hz ± 5%.
  • Output: Available in 24 VDC, 48 VDC, and 110 VDC with floating voltages of 27.2 VDC, 54.4 VDC, and 112.5 VDC respectively.
  • Technology: Rectified, controlled filtered technology with electronic current limitation and short-circuit protection.
  • Regulation: ± 1% steady state with residual ripple < 5%.
  • Protection: Includes bipolar fuses, thermal protection, and resistance to shock and vibration.
Mechanical Characteristics:
  • Cases range from CFE20 to CFE250 with dimensions varying from 400x300x200 mm to 1200x800x400 mm.
  • Metal case with IP 23 rating, polyester finish, and salt atmosphere resistance.
Options and Standards:
  • Additional outputs, voltage threshold control, and temperature probes available upon request.
  • Complies with EC Marking and Bureau Veritas certification.
Applications: Suitable for marine, offshore, military, railway, and industrial applications, ensuring robust performance and reliability.
See more

Catalog excerpts

CRM range – 24/48/110V – Single phase-1

Thyristor controlled battery chargers - CRM Range •iN/VC Using thyristor controlled technology, compact and lightweight, the CRM range battery chargers can be associated with any battery technology (recombined sealed lead, open lead, calcium lead, classic lead, nickel cadmium batteries ...)■ They insure the charging and maintenance of the batteries and an adequate current for the outputs. Using robust and reliable thyristor technology, they can be used in numerous applications: marine - offshore - military -railway - industry. Bureau Veritas certificate of type approval n° 04682/C0 BV

 Open the catalog to page 1
CRM range – 24/48/110V – Single phase-2

Main technical specification Input: • 230 Vac or 400 Vac ± 10% 576 single phase according to model. • Frequency : 50 to 60 Hz +/- 5% • Other voltages, frequency: upon request. Output: • 24 Vdc - floating voltage: 27, 2 Vdc. • 48 Vdc - floating voltage: 54,4 Vdc • 110 Vdc - floating voltage: 112.5 Vdc • Other voltages: upon request. Technology: • Rectified, controlled filtered technology. • Filtered direct current (possible operation as power supply). • Electronic limitation of the output current. • Short-circuit possible without any damage to the equipment. • Designed to reduce interferences...