Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10
12Pages

{{requestButtons}}

Catalog excerpts

Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 1

Power-D-Box® with pcb-mounted sockets Description The Power-D-Box® with printed circuit board is a compact power distribution system, designed as a 2U 19“ rack, made of aluminium profiles with anodised front plate. It accommodates the following circuit breaker types: thermal magnetic types 3600 / 3900 or 2210 (1-pole or 2-pole) and electronic circuit breakers type ESS20 or ESX10. 30 single pole ways (15 x 2-pole ways) are available as a redundant or non-redundant system. The integral group signalling is optionally working as series connection of the make contacts or parallel connection of the break contacts. The entire internal circuitry is on printed circuit board. Type number PDB-P-L 19“ Power-D-Box® with printed circuit board, positive pole protected Suitable plug-in circuit breaker types 2210 circuit breaker type 2210 3600 circuit breaker type 3600 or 3900 ESS20 electronic circuit breaker ESS20 ESX10 electronic circuit protector ESX10 Number of protected poles _ 1-pole protected (standard) 2P 2-pole protected (only with 2210) Supply and load terminals on pcb 30A0 1 x 30 breakers (1-pole), not redundant 30R0 2 x 15 breakers (1-pole), redundant 28R0 2 x 7 breakers (2-pole), redundant Supply and load terminals on symmetrical rail 30A3SW 1 x 30 breakers (1-pole), not redundant 30R3SW 2 x 15 breakers (1-pole), redundant 28R4SW 2 x 7 breakers (2-pole), redundant Signalling, terminals on pcb B1_make contact connected in series B4 make contact connected in series and break contact connected in parallel Signalling, terminals on symmetrical rail B1GR make contact connected in series B4GR make contact connected in series and break contact connected in parallel

Open the catalog to page 1
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 2

Technical Data Less wiring time through pcb design Small installation depth of 205 mm or 250 mm for use where space is at a premium Removable front plate with captive screws and imprinted marking 30 slots for thermal-magnetic or electronic circuit breakers in a Power-D-Box® Redundancy possible with 2 x 15 ways 1-pole or 2 x 7 ways 2-pole Circuit breaker can be plugged in later (even with the system on - hot-swap capability) Screw terminals directly on the pcb (only positive pole), optional additional terminal on rear-side symmetrical rail with additional negative pole patching Supply for...

Open the catalog to page 2
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 3

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Available terminal designs Version for supply terminals load terminals Ground terminals (studs) Schematic diagram for 1-pole versions Schematic diagrams: for 2210 / 3600 / 3900, not redundant pcb terminals on symmetrical rail (A3 / R3)

Open the catalog to page 3
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 4

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Schematic diagram for 1-pole versions Schematic diagrams: for 2210 / 3600 / 3900, redundant pcb terminals on symmetrical rail (A3 / R3) Schematic diagram for 1-pole versions, ESS20 Schematic diagrams: for ESS20, not redundant pcb terminals on symmetrical rail (A3 / R3)

Open the catalog to page 4
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 5

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Schematic diagram for 1-pole versions, ESS20 Schematic diagrams: for ESS20, redundant pcb terminals on symmetrical rail (A3 / R3) Dimensions Views / dimensions: front view all versions

Open the catalog to page 5
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 6

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Dimensions pcb Top view / dimensions: terminals on pcb Rear view: terminals on pcb, redundant supply B

Open the catalog to page 6
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 7

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Dimensions symmetrical rail Top view / dimensions: terminals on symmetrical rail, not redundant load terminals A Rear view: terminals on symmetrical rail, not redundant

Open the catalog to page 7
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 8

Top view / dimensions: terminals on symmetrical rail, not redundant Imwimppp itnfdiwpipp Inn n n ]ln n n n j!Lo n n lira n n In n n n .A: Rear view: terminals on symmetrical rail, not redundant

Open the catalog to page 8
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 9

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Schematic diagram for 2-pole versions, redundant Schematic diagrams: for 2210, redundant pcb terminals on symmetrical rail (R4) Dimensions blanking pieces Views / dimensions: front view all versions

Open the catalog to page 9
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 10

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Dimensions Top view/dimensions: terminals on pcb, redundant cable grip rail top cover (perforated) Rear view: terminals on pcb, redundant supply B

Open the catalog to page 10
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 11

Flexible Power-D-Box® with pcb for 3600/2210/ESS20/ESX10 Dimensions Top view/dimensions: terminals on symmetrical rail, redundant signalling A Rear view: terminals on symmetrical rail, redundant

Open the catalog to page 11
Flexible Power-D-Box® with pcb for 3600/2210/ ESS20/ESX10 - 12

Blanking piece for Power-D-Box (types ESS20/ESX10) Y 308 563 41 Jumper to bypass looped through unused auxiliary contacts (series connection) X 222 066 01 This is a metric design and millimeter dimensions take precedence ( mm ) All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.

Open the catalog to page 12

All E-T-A Elektrotechnische Apparate catalogs and brochures

  1. MPR10

    4 Pages

  2. SVS14

    6 Pages

  3. SVS15

    8 Pages

  4. SVS16

    6 Pages

  5. SVS18

    6 Pages

  6. SVS20

    8 Pages

  7. PP-M-PM024

    6 Pages

  8. PP-M-DC024

    6 Pages

  9. E-1048-8D...

    4 Pages

  10. 3131-A

    6 Pages

  11. ESR10

    4 Pages

  12. 1620

    2 Pages

  13. D_8340-G2

    5 Pages

  14. D_1120

    3 Pages

  15. D_1110

    2 Pages

  16. E-1048-8D

    3 Pages

  17. E-1048-8I

    5 Pages

  18. E-1048-8C.

    4 Pages

  19. 8340-F

    6 Pages

  20. 8340-G2

    5 Pages

  21. 1610-21

    3 Pages

  22. 1110

    2 Pages

Archived catalogs