1. Catalogs
  2. DEIF
  3. Insulation monitors, AAL-2
video corpo

Insulation monitors, AAL-2

Insulation monitors, AAL-2

Insulation monitors, AAL-2

Product catalog summary
Overview: The document provides detailed specifications and operational guidelines for the AAL-2 Insulation Monitor, designed to continuously monitor insulation resistance between an AC network and protective ground.
Specifications: The AAL-2 operates with a measuring output voltage of 12 V DC and can handle an AC input voltage up to 528 V AC. It features a DC resistance of 22 kΩ or 220 kΩ and an AC impedance greater than 100 kΩ at 50 Hz. The device supports a frequency range of 45 to 500 Hz and has a response time of less than 0.5 seconds for 1 MΩ and less than 3.5 seconds for 10 MΩ.
Functionality: The AAL-2 includes a green power indicator and a red warning indicator. The warning indicator activates when the measured resistance falls below the set point, triggering a relay. The relay can be configured as normally energised (NE) or normally de-energised (ND), depending on the application requirements.
Advanced Features: The device offers delay functionalities to reduce false warnings, including a power-on delay of 3 seconds and a warning on delay of 0 or 4 seconds. The set point can be adjusted using a screwdriver, and the relay function and warning delay can be modified on-site using jumpers.
Standard Products: Three standard configurations are available, each with specific measuring ranges, relay types, and warning delays. Custom configurations can be ordered if standard options do not meet specific needs.
Technical Specifications: The AAL-2 is tested for temperature, climate, vibration, and shock resistance according to IEC standards. It is designed for installation category III and pollution degree 2, with various EMC compliance certifications.
Safety and Approvals: The device is constructed with self-extinguishing plastic parts and offers IP52 protection, with optional IP54. It is approved and certified according to relevant international standards.
Contact Information: DEIF A/S, Frisenborgvej 33, DK-7800 Skive, Denmark. Tel.: +45 9614 9614, Email: [email protected].
See more

Catalog excerpts

Insulation monitors, AAL-2-1

TCM-2 Thyristor Control Module TCM-2 ThyristorSHEET Module DATA SHEET DATA Control DATA SHEET Insulation monitors, AAL-2 • Warning delay and power-up delay • Indication of set point on front • Measuring range up to 440 V AC

 Open the catalog to page 1
Insulation monitors, AAL-2-2

Data sheet Application The AAL-2 continuously monitors the insulation resistance between the connected AC network (IT network) and protective ground (PE). Due to the warning delay functionality, the AAL-2 can be used in applications with some capacitance. Measuring principle 12 V DC is superimposed on the system that is monitored, and the resulting current is measured. Basic operation The functionality of the product is to measure and monitor the insulation resistance between the network and PE. Functionality The green power indicator will be ON when auxiliary power is connected. The insulation...

 Open the catalog to page 2
Insulation monitors, AAL-2-3

Data sheet Advanced functionality Delays To minimise the number of unwanted warnings, delay functionalities are available in the product. Description When powering up the product Delay between warning indication and relay operation By means of a jumper it is possible to select between no warning delay or 4 s warning delay. The shown 22 kΩ set point will accept capacitance up to 260 µF on 1 MΩ range, without false warning. For higher capacitive load, the set point will have to be decreased accordingly. If the resulting set point is unacceptably low, it is recommended to apply a Selectable Insulation...

 Open the catalog to page 3
Insulation monitors, AAL-2-4

Data sheet Standard products The following products are “off-the-shelf” products with very short delivery times and optimised prices. AAL-2, Standard 1: • • • • Measuring range/scale: 10 to 0 MΩ (corresponding to 0.22 MΩ at scale centre) Red marker pointer NE relay Warning delay: 4 seconds Measuring range/scale: 10 to 0 MΩ (corresponding to 0.22 MΩ at scale centre) Red marker pointer ND relay Warning delay: 4 seconds Measuring range/scale: 1 to 0 MΩ (corresponding to 22 KΩ at scale centre) Red marker pointer ND relay Warning delay: 4 seconds It is not possible to change the configuration of these...

 Open the catalog to page 4
Insulation monitors, AAL-2-5

Data sheet Warning: If a high-voltage "MEGGER" is used, the AAL-2 must be disconnected at terminal "P" before testing is carried out. Omitting this may result in damage to the AAL-2.

 Open the catalog to page 5
Insulation monitors, AAL-2-6

Data sheet Technical specifications Technical specifications DC resistance (Ri): Measuring output voltage: 25/250 uF (depending on settings - see table) Frequency range: 0 to 150 kΩ (if set point above 150 kΩ is selected, warning relay will be disabled) 0 to 1.5 MΩ (if set point above 1.5 MΩ is selected, warning relay will be disabled) Change-over contact Standard: Normally de-energised (ND). Optional: Normally energised (NE) Contact ratings: AC1: 8 A, 250 V AC – DC1: 8 A, 24 V DC AC15: 3 A, 250 V AC – DC13: 3 A, 24 V DC 7 5 Mechanical life: 2 × 10 operations, electrical life: 1 × 10 operations...

 Open the catalog to page 6

All DEIF catalogs and brochures

  1. AWC 400

    36  Pages

  2. AKR 3

    10  Pages

  3. AGC 150 ATS

    4  Pages

Archived catalogs

  1. AMC 600

    38  Pages

  2. GPU -3

    17  Pages

  3. DBC-1

    13  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.