1. Catalogs
  2. DEIF
  3. Insulation monitor, ADL-111Q96
video corpo

Insulation monitor, ADL-111Q96

Insulation monitor, ADL-111Q96

Insulation monitor, ADL-111Q96

Product catalog summary
Overview: The document is a technical data sheet for the ADL-111Q96 insulation monitor by DEIF A/S, designed for monitoring insulation resistance in DC networks. It is applicable for marine installations and other insulated voltage networks.
Specifications: The ADL-111Q96 is available in standard and advanced versions, supporting network voltages of 24 V, 110 V, and 220 V DC. The standard version measures resistance up to 500 kΩ with a maximum capacitance of 20µF, while the advanced version measures up to 10 MΩ with a capacitance of 120µF.
Measuring Principle: The device monitors insulation between the negative conductor and the safety cable using alternating polarity DC voltage. It compensates for network capacitances and DC components automatically.
Indicators: The device features a meter for resistance value, a red LED for fault indication, and a green LED for supervision status.
Relay Output: The ADL includes a change-over relay contact configurable to normally energised (NE) or normally de-energised (ND) states, with NE recommended for alarms.
Technical Specifications: The device operates within a temperature range of -10 to 55 °C and offers protection ratings of IP52 or IP54. It is CE-marked and complies with various EMC standards.
Connection and Testing: The auxiliary supply should be protected by a 2 A fuse. For high-voltage testing, the measuring wire must be disconnected.
Dimensions and Weight: The device has a panel cutout of 92.0 × 92.0 mm and weighs approximately 0.390 kg.
Ordering Information: The document provides item numbers and descriptions for different product variants and available options such as anti-glare glass and IP54 protection.
See more

Catalog excerpts

Insulation monitor, ADL-111Q96-1

Data sheet Insulation monitor, SIM-Q/SIM-Q LF TCM-2 Thyristor Control Module TCM-2 Thyristor Control Module DATA SHEET DATA SHEET DATA SHEET Insulation monitor, ADL-111Q96  Monitoring of insulation resistance on a DC network  24 V, 110 V or 220 V DC  Accepts up to 120µF leakage capacitance

 Open the catalog to page 1
Insulation monitor, ADL-111Q96-2

Data sheet Application The ADL is used for supervision of the insulation resistance between an insulated voltage distribution network (IT network) and earth cable/safety cable. The instrument is applicable in conjunction with DC networks of 24 V, 110 V or 220 V DC. This type of insulation measurement is only carried out on DC networks where both conductors are isolated from the protective earth/the hull of the ship. The ADL can be used for marine installations and other types of insulated voltage networks, for example DC manoeuvre voltages of transformer stations. Measuring principle The insulation...

 Open the catalog to page 2
Insulation monitor, ADL-111Q96-3

Data sheet Product variants The ADL is available in two different versions – standard and advanced. Standard versions: Type Network/aux. voltage Measuring range 1µF or 20µF maximum capacitance on network (user-selectable via S1 under the rear cover). See ADL Quick guide. Set point adjustment from ohm scale at the rear of the instrument. Set point The requested alarm limit value is set on an ohm scale at the rear of the instrument.

 Open the catalog to page 3
Insulation monitor, ADL-111Q96-4

Data sheet Advanced versions: Type Network/aux. voltage Measuring range 1µF to 120µF maximum capacitance on network (selectable via S1 under the rear cover). See ADL Quick guide. Set point is automatically visible on front scale during power-up and adjustment. Due to the low injection voltage, problems with activation of possible over-voltage protections are eliminated. Set point A new feature makes accurate setting of set point much easier. When the set point potentiometer at the rear of the instrument is turned, the product automatically goes to meter indication of set point during setting...

 Open the catalog to page 4
Insulation monitor, ADL-111Q96-5

Data sheet Technical specifications Standard range: Network voltage Range - Measurement - Scale - Set point Product variant Response time Response time Injection voltage Response time Response time Response time Injection voltage Advanced range: Network voltage Range - Measurement - Scale - Set point Product variant General technical specifications Meter - Accuracy - Temperature drift - Aux. supply influence - Accuracy - Reproduceability - Hysteresis - Temperature drift - Aux. supply influence - Temperature drift - Voltage drift - Relay output Contact rating Relay coupling ±5 % of scale length...

 Open the catalog to page 5
Insulation monitor, ADL-111Q96-6

Data sheet Connection diagram + DC Source Test resistance Instrument shown as self powered * recommended values The auxiliary supply should be protected by means of a 2 A fuse. Test If a periodical test function is required, it can be achieved as shown in the connection diagram above. Warning If the installation is to be tested by means of a high-voltage "MEGGER", the measuring wire to the ADL must be disconnected before testing is carried out.

 Open the catalog to page 6
Insulation monitor, ADL-111Q96-7

Data sheet Available variants Type Available options Option Anti-glare glass IP54 protection incl. rubber gasket Glass with red adjustable pointer (IP52 only) Red pointer, individually adjustable Order specifications Product variants Mandatory information Item no. Additional options to a standard variant Variant no. Example: Mandatory information Additional options to a standard variant Due to our continuous development we reserve the right to supply equipment which may vary from the described. DEIF A/S, Frisenborgvej 33 DK-7800 Skive, Denmark Tel.: +45 9614 9614, Fax: +45 9614 9615 E-mail: deif@...

 Open the catalog to page 7

All DEIF catalogs and brochures

  1. AWC 400

    36  Pages

  2. AKR 3

    10  Pages

  3. AGC 150 ATS

    4  Pages

Archived catalogs

  1. AMC 600

    38  Pages

  2. GPU -3

    17  Pages

  3. DBC-1

    13  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.