Applications: The Front Terminal AGM 12V Series batteries are primarily used in telecom stations, power stations, and network connection equipment for communication systems. They are designed to fit standard 19-inch or 23-inch power cabinets.
Specifications:
  • Capacity range: 55 to 200Ah
  • Voltage: 12V
  • Low self-discharge rate: ≤3% per month
  • High oxygen recombination efficiency: ≥98%
  • Design lifetime: 10 to 12 years in standby applications at 25°C
  • Operating temperature range: -15°C to +45°C
  • Deep cycle performance: up to 1500 cycles at 30% Depth of Discharge (DOD)
  • Construction: Thick flat plate with high Tin low Calcium alloy, fire-resistant ABS container
  • Front access terminal suitable for 19” and 23” ETSI racks
Features: The CSPOWER Front Terminal lead acid battery is designed for the communication industry, featuring a slim shape and front terminal connection for easy installation and maintenance. It offers high rate discharge performance due to its radial grid design and tight assembly technology.
Model Specifications: The document lists various models with their respective voltage, capacity, dimensions, weight, terminal type, and bolt specifications. For example, the FT12-55 model has a capacity of 55Ah, dimensions of 277x106x223 mm, and weighs 16 kg.
Charging and Performance Characteristics:
  • Recommended constant voltage charging
  • Float voltage range: 13.6 to 13.8 V/PC at 20~25°C
  • Cyclic application charge voltage: 14.4 to 14.9 V/PC at 20~25°C
  • Maximum charge current allowable: 0.25C
Additional Characteristics: The document discusses the effects of temperature on service life, capacity, and self-discharge, emphasizing the battery's adaptability to various demands such as Telecom, UPS, and Solar applications.
See more

Catalog excerpts

CSPower Telecome Gel Battery- FT series-1

TELECOM BATTERY FRONT TERMINAL AGM 12V SERIES CSPOWER Front Terminal lead acid battery is mainly used in the area of communication, which is novel in design, reasonable in structure and occupying the leading position in the same industry of the world. This AGM battery for telecom industry comes with slim shape design and front terminal connection. Thus, easy installation and maintenance can be ensured and space can be saved. Radial grid design plus tight assembly technology assures this rechargeable battery prominent • Capacity range: • Voltage: 55 ~ 200Ah 12V • High oxygen recombination efficiency: 10~12 years design lifetime in standby application at 25 °C • Wide operation temperature range: • Deep cycle performance: up to 1500 cycles@30% DOD • Thick flat plate with high Tin low Calcium alloy • Fire resistance ABS containery • Front access terminal with standard width for 19" and 23" ETSI racks; TELECOM BATTERY (FRONT TERMINAL AGM 12V SERIES) For standard 19 inches or 23 inches power cabinets Network connection equipment of communication systems Specifications -Terminal Bolt Products will be improved without notice, please contact sales for specification in kind prevail.

 Open the catalog to page 1
CSPower Telecome Gel Battery- FT series-2

TELECOM BATTERY (FRONT TERMINAL AGM 12V SERIES) Charging volfegr: 13.65*4.1 V pierr *1 IP'C front term ce can be e ny deman ♦ Cycle Life VS. Depth of Discharge(25C) Battery Construction ♦ Temperature Effect on battery self-discharge Temperature effect on battery self-discharge Storage lime (month) Charging voltage and settings for stationary battery • Constant voltage charging is recommended • Float voltage range: 13.6 to 13.8 V/PC@ 20~25°C • Cyclic application charge voltage : 14.4 to 14.9 V/PC @ 20~25°C • Max. charge current allowable : 0.25C

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.