1. Catalogs
  2. Caterpillar Marine Power Systems
  3. C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)
video corpo

C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)
1 /2Pages

C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)

C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)
1 /2Pages

Catalog excerpts

C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)-1

STANDARD ENGINE EQUIPMENT • Crankcase ventilation system • Common Rail fuel system • 12V and 24V starter motor and battery charging alternator • Mounted air cleaner • Integral plate-type oil cooler • 3-phase AREP generators which provide the functionality of a permanent magnet excitation system • EMCP4.2 control panel with remote monitoring capability • Isolated sump • Anti-vibration engine mounts • Glowplugs aid starting in cold weather • Gear-driven sea-water and jacket-water pumps • Safety shutdowns for low oil pressure, high water temperature, and overspeed • Worldwide Extended Service Coverage (ESC) available • 7 available ratings to cover power demand of both 50 Hz and 60 Hz • Watercooled exhaust manifold and turbocharger Image shown may not reflect actual engine • EPA Tier 3/IMO compliant/CCNR Stage 2 Right Side • 7.01 liter displacement • 50 Hz 1500 rpm/60 Hz 1800 rpm rated engine speed • 105 mm (4.13 in) bore x 135 mm (5.32 in) stroke • Turbocharged-aftercooled aspiration • Electronically governed • Heat exchanger or keel cooled • Refill capacity – Cooling system: 8 L (10.0 U.S. gal) — hex 3 – Lube oil system: 21 L (5.6 gal) • Counterclockwise rotation from flywheel end • 500-hour oil change interval ENGINE DIMENSIONS & WEIGHT (1) Length (3) Height Weight, Net Dry (approx) Note: Do not use these dimensions for installation design. See general dimension drawings for detail.

 Open the catalog to page 1
C7.1 Spec Sheet (100,118,150 ekW 50 Hz / 118,150,175,200 ekW 60 Hz)-2

MARINE ENGINE PERFORMANCE 50 Hz % Load OPTIONAL ATTACHMENTS • ontrol System C Governor droop kit (selecting this kit enables paralleling with appropriate customer-supplied switchgear) • Generators & Generator Attachments Space heater kit, installed — 120V AC, 240V AC • uel System F Double wall fuel lines with enclosed common rail and mounted alarm reservoir, duplex fuel filters • ube System L Duplex oil filters • tarting System S Additional 12V or 24V electric starter, air starter, jacket water heater options • arine Classification Society (MCS) Approval – M Pending ABS, BV, DNV, LR, GL, PRS,...

 Open the catalog to page 2

All Caterpillar Marine Power Systems catalogs and brochures

  1. C12 ACERT

    5  Pages

  2. pl1000e

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.