Catalog excerpts
DUCT SMOKE DETECTORS Hi-Temp, Low-Flow & No-Tools PRODUCT APPLICATION The SL-2000 Series Smoke Duct Detector is the latest innovation for early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial, Industrial, and Residential applications. The unit is designed to prevent the recirculation or spread of smoke by air handling systems, fans and blowers. Complete systems may be shut down in the event of smoke detection. The SL-2000 is designed and built to meet all local code requirements, as well as the NFPA and ICC standards regarding HVAC supply and return duct smoke detectors. Output terminals are provided for a wide range of remote accessories such as horns, strobes, remote status indicators, and test/reset key switches or push buttons. PRODUCT DESCRIPTION The SL-2000 includes many features that represent true innovations from current generation duct smoke detectors. Our traditional installer/servicer-friendly approach has been closely followed and expanded throughout the SL-2000. This philosophy provides a new level of efficiency in after-purchase value to both the installer/servicer and end-user. Our attention to detail has yielded a host of “No-Tools Required” features, as well as a multi-application performance CSFM LISTED MEA ACCEPTED level as yet unmatched in the industry. Innovative product combined with unsurpassed customer service equals the right combination for all of your projects. The key features below detail many of the customer-driven innovations incorporated in the SL-2000 Series. FEATURES Low-Flow Technology: Both Ionization and Photoelectric models listed for velocities between 100-4000 ft./min Both models listed for high-temperature applications Operating voltages: 230VAC, 115VAC, 24VAC, 24VDC Interconnect up to 30 units for common functions Patented “No-Tools Required” front or rear loading and removing sampling/exhaust tubes Patented “Test Port Valve” allows for aerosol smoke testing without cover removal Clear cover fitted with four captive “No-Tools Required” thumbscrews Instantaneous cover removal trouble indication Staggered terminal blocks for easier wiring Flashing LED on detector head indicates normal operation Magnet test capability (magnet included) More wiring space than competitive models Footprint allows easy retrofit in many applications without additional drilling Over 15 remote accessories available Duct wall gaskets on back of enclosure are pre-installed Air Products and Controls Inc. 1749 E. Highwood Pontiac, MI 48340 (248) 332-3900 Phone (888) 332-2241 Toll free (248) 332-8807 Fax www.ap-c.com Compatible with the WP-2000 weatherproof enclosure Reset switch is also an alarm test switch - competitive models require a magnet or cover removal to test at unit Unit includes green pilot and red alarm visual indicators External mounting tabs do not require cover removal to install Colored cover gasket indicates proper cover seal UL, CUL, CSFM, and MEA Listed Compact, lightweight size means easy handling, lower shipping costs Two sets of 10A form “C” alarm contacts One set of 2A form “A” alarm contacts One set of 10A form “C” trouble contacts Large terminal connection screws Standard interchangeable “plug-in” UL268 photoelectric or ionization heads Advanced detector head design yields internal dust filtering No additional screens or filters to clean Compatible with building automation and fire alarm systems Ionization and Photoelectric versions available Complete wiring details perm
Open the catalog to page 1_REMOTE ACCESSORY WIRING_ Make sura to use only Air Products and Controls brand UL Ustad Ramota Accessorise INTERCONNECTION WIRING / COMMON FUNCTIONS Make sure to use a common Independent power suppr/ SHOWN IN NON-ENERGIZED CONDITION. - UNDER NORMAL OPERATION /-\_ CONTACTS WILL BE REVERSED ALARM ALARM LINK CONTACT TEST / RESET' TEST / RESET All alarm relays operate with single alarm. Individual horn/strobe units operate on alarmed detector only. PRODUCT SPECIFICATIONS TROUBLE CONTACTS TO FIRE ALARM PANEL WHEN USING THIS OPTION SLAVE RELAY All alarm relays operate with single alarm. All...
Open the catalog to page 2All Apollo Fire Detectors catalogs and brochures
-
Polycarbonate Pull Station
2 Pages
-
Marine fire detection
2 Pages