Polycarbonate Pull Station
2Pages

{{requestButtons}}

Catalog excerpts

Polycarbonate Pull Station - 1

I WORLD CLASS FIRE SOLUTIONS Dual Action Addressable Manual Pull Station The Dual Action Addressable Manual Pull Station is a state-of-the-art, dual-action device (i.e., requires two motions to activate) that includes an addressable interface for Apollo compatible addressable fire alarm control units (FACUs). Because the initiating device is addressable, the control unit can display the exact location of the activated station. This leads fire personnel quickly to the location of the alarm. Table 1 Part Number and Descriptions • Maintenance personnel can open station for inspection and address setting without causing • Status LED (red) is visible through the face of the station, flashes in normal operation and latches steady when in alarm. Flashing when polled is • The "PUSH" handle latches in down position, revealing a yellow stripe to clearly indicate the station has been operated. • Terminal screws are wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). Dual Action Addressable Manual Pull Station & Back Box • Can be surface mounted (using Back Box Part No. 56000-006) or semi flush mounted. Semi-flush mounts to a standard single gang electrical box. • Highly visible, attractive shape and textured finish with smooth dual-action design. • Lightweight, durable polycarbonate construction. • Meets ADAAG controls and operating mechanisms guidelines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Meets UL 38, Standard for Manually Actuated Signaling Boxes. Email: SalesUSA@apollo-fire.com Overseas offices: UK China

Open the catalog to page 1
Polycarbonate Pull Station - 2

Technical Data Operating Voltage 17 - 28 VDC 20 - 28 VDC UL Listed to: Current Consumption at 24V Standby 200µA Alarm Current 3.6mA + Quiescent Installation Product will mount semi-flush into a single-gang electrical outlet box, or will surface mount to the model 56000-006 Surface Back Box. Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the activated flag (in bright yellow) appears at the bottom of the station face. To reset the station, simply unlock the station with the key and allow the door to open. This action...

Open the catalog to page 2

All Apollo Fire Detectors catalogs and brochures