8 - HIDDEN PARAMETERS
Parameter C30 (LSI) It sets out the Inversion Maximum Limit (LSI).
Default=2° C
It can be changed from 1 to 4° C.
This limit represents the °C above the Set Point when there is an inversion to the Cool
Mode.
For example:
C30=2° C
Set Point=25° C
Change from Heat to Cool Mode=27° C arameter C30 When the panel is off
Press the S button + the Off button (for 3 seconds) > [PASS] > Press the S button >
[0] > Press the
Arrow for boat Up or the Arrow Down to display the number 123 > Press the S
button > [C10] > Press the Arrow Up or the Arrow Down button to display the param-
eter [C30] > Press the S button > Press the Arrow Up or the Arrow Down button to dis-
play the new desired value > Press the S button to confirm Parameter C40 It sets out the inversion Minimum Limit (LII).
Default=2° C
It can be changed from 1 to 4° C.
This limit represents the ° C below the Set Point when there is an inversion from the
Cool to the Heat Mode.
For example:
C40=2° C
Set Point=25° C
Change from Cool to Heat Mode=23° C How to modify the p arameter C40 When the panel is off
Press the S button + the Off button (for 3 seconds) > [PASS] > Press the S button >
[0] > Press the Arrow Up or the Arrow Down button to display the number 123 > Press
the S button > [C10] > Press the Arrow Up or the Arrow Down button to display the
parameter C40 < Press the S button > Press the Arrow Up or the Arrow Down button
to display the new desired value > Press the S button to confirm Parameter C50 (Default=5) In Unattended Mode it increases (in cool cycle) or decreases (in heat cycle) the
parameter C50 Set Point.
It can be changed from 1 to 10° C.
For example:
C50=5° C
Mode=Cool
Set Point=25° C; Set Point Unattended=25+5=30° C
Mode=Heat
Set Point=25° C ; Set Point Unattended=25-5=20° C How to modify the p arameter C50 When the panel is off
Press the S button + the Off button (for 3 seconds) > [PASS] > Press the S button >
[0] > Press the Arrow Up or the Arrow Down button to display the number 123 > Press
the S button > [C10] > Press the Arrow Up or the Arrow Down button to display the
parameter [C50] > Press the S button > Press the Arrow Up or the Arrow Down but-
ton to display the new desired value > Press the S button to confirm Pag. 13 >