CWS Basic 121-161-201-251

4- COMMISSIONING

4.4 Fan coil

Check that each fan coil is correctly fed with chilled water, measuring the inlet and out-let temperatures. The difference between the two temperatures should be between 5° C and 10° C. If the differential is higher, it normally means that there is still air in the circuit and the circulation in that fan coil is poor. In case of particularly long circuit, it might be necessary to adjust the fan coil flow clo- sing the calibrating valves of the fan coils nearer to the manifold in order to let more water to reach the ones, which are more distant. Check that the thermostat sensor is correctly positioned in the air intake of each fan coil. If the temperature control is "Fan only", the thermostat stops the fan when the ambient temperature reaches the set point. IMPORTANT: With the "Fan only" control, the thermostat sensor must be installed on the air intake but not on the fan coil. If the fan coil control is "Water valve" then the thermostat closes the special water valve connected to the fan coil while the fan keeps running. In this case the thermo- stat sensor must be installed on the fan coil fastened to the special thermostat bulb holder.
Page 12
NauticExpo's Virtual Library: PDF Catalogues | Documentation | Boating Brochures | Manuals | Marine directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24
page 25 p.25
page 26 p.26
page 27 p.27
pdf-page pdf ne En 2009-11-48-24