CWS Basic 121-161-201-251
4- COMMISSIONING >
4.2 Start up
Give supply to the main control box.Turn the "Mode" switch to the "Cool" or "Heat" position.
Check that both
pumps for boats have an even flow.
As the compressor runs, the fresh water temperature will begin tocool down (if the unit is in "Cool" mode) or to heat up (if the unit is in
"Heat" mode). As the fresh water temperature is approaching the set
point ("Cool" mode = +12° C, "Heat" mode = +40° C) the thermostat
will stop the compressor. The speed at which the water cools down depends from several fac-tors, as the number and capacity of fan coil connected, the fan coil
speed, the room temperature, etc….; therefore this value is not a
valuable parameter. >
4.3- Sea water circuit
Check that the sea-water intake is fully open
and that the flow is even. >
Page 11