116-P-BS320/CE - Rev. F, 2005-05-31 Protecting life, environment and property...
Features
Self-Verify function for automatic testing of detectors
Automatic addressing of detectors
Accommodates up to a maximum of 12 modules, of which
maximum six can be Loop Driver Modules
User-friendly display and operator controls
Backlit operational buttons. Text display suitable for full
darkness operation
Surface or flush mounting, or rack mounting in standard
19 cabinets
Designed to meet EN-54 and LPCB requirements, and
conforms to CE standards
Complies with environmental conditions of IEC-721-3-3
class 3k5
Application/Description
BS-310/320 is a complete fire alarm control panel with full operation
capabilities. The panel serves as an operating panel for
one or several defined operation zones. All alarm handling and
system features can be controlled and monitored from the
panel.
The panel can accommodate up to a maximum of 12 modules.
The system offers a Loop Driver Module for detector loops and
several types of I/O modules for monitored outputs, open collector
outputs, galvanic isolated inputs and monitored inputs.
There can be a maximum of six Loop Driver Modules in each
panel. All modules are easily plugged onto each other on a
standard mounting rail inside the unit.
The panel is menu operated on a 16-line display, with 40 characters
per line. A built-in printer is available as an option.
With a LON Interface the Fire-Alarm Control Panel can communicate
with other system units on the local operating network,
AutroLON. This interface is standard in BS-320, and not
included in BS-310. The panel has a 230VAC/3A power module
for battery charging, and a built-in emergency battery.
Indicators
16 x 40-character alphanumeric display
Fire/Alarm, More Events, Fault, Function Disabled, Function
Delayed, Fire Brigade Signaled, Power, Testing, Fire Brigade
Disabled, Fire Brigade Fault, System Fault, Alarms Disabled,
Alarms Fault
Internal buzzer
Operator Controls
More Events, Mute Panel, Silence Alarms, Reset
Keyboard with alphanumeric characters and scroll function
Separate buttons for menu operation
Backlit buttons and text
Optional I/O Modules
Loop Driver Module (BSD-310/311). For connection of detector
loops. One detector loop can be connected to each module.
A maximum of 127 loop units (detectors, manual callpoints,
I/O-units and/or electronic sounders) can be connected
to each detector loop
Output Module (BSB-310), with four monitored outputs. For
connection to fire-alarm devices (FAD), such as sounders
etc., and fire-protection equipment (FPE) such as fire doors,
ventilation controllers or fire extinguishers. Also suitable for
connection to fire-alarm routing equipment (FARE), such as
fire brigade equipment, and for connection to fault outputs
Output Module (BSJ-310), with eight open collector, nonmonitored
outputs. For connection of external LED-indication
panel
Input Module (BSE-310) with four monitored inputs
Input Module (BSE-320), with eight non-monitored inputs
(galvanic isolated)
Capacity
There can be a maximum of 32 panels in a LON ring (EN-54).
A demand for more than 32 panels requires several LON
rings
Each unit can be equipped with a maximum of 12 of the
above modules, of which maximum six can be Loop Driver
Modules (cabinet without internal batteries)
A maximum of 512 detectors and manual call-points can be
connected to each Fire-Alarm Control Panel (EN-54)
AutroSafe Fire-Alarm Control Panel BS-310/320
|
|