P-BX-10/CE . Rev. B, 030122 Protecting life, environment and property...
Features
Modern and user-friendly design.
Simple installation.
4 conventional detection zones, monitored for
break/short circuit, each with a capacity for up to 32
detectors.
Alarms/error warnings notified with LEDs on the front
panel and alarm/error outputs.
Easy-to-operate using the keypad.
«Key-less» operation.
Password-protected operator mode.
Keypad with background light for operation in dark sur
roundings.
Digital inputs for technical alarms.
Inputs for remote disablement of detection zones.
Remote reset of control panel
Simple activation of immediate alarm disabled
(day/night function).
Application
The BX-10 fire alarm control panel is a modern
conventional panel designed for minor installations.
Among several applications, the BX-10 is especially suitable
for day-care centres, schools, smaller stores, industrial
buildings, smaller overnight stops, farm buildings and
for automatic and distant telecommunication installations.
BX-10M (M stands for Maritime version) is also suitable for
fishing boats, work boats, yachts and smaller cargo boats.
The system covers 4 conventional detection zones. Up to
32 detectors/manual call-points can be connected to each
zone. Manual call-points and automatic detectors can be
connected to the same zone. A disablement of a zone will
not disable the manual call-points in the disabled zone.
The control panel provides an integrated temperature compensated
power supply and emergency batteries.
Detection zones, alarm outputs and controls can be disabled
from the front panel.
BX-10 can work together with all types of Autronica standard
conventional detectors.
The control panel complies with EN-54 requirements and
meets the EMC requirements for CE standards. For maritime
installation, the panel complies with SOLAS convention,
and meets the maritime requirements.
Inputs/outputs
Inputs:
4 zone circuits for detectors, single loop with endload.
4 inputs for connection of zone disablement switches.
Input for remote activation of sounders
(evacuation/school bell).
Input for remote control of day/night function
(immediate alarm disabled).
Input for remote disablement of alarm outputs
(sounders).
Input for remote sounder silence.
Input for remote system reset.
230V AC mains power connection.
Outputs:
24V DC / 0,63A to external equipment.
12V DC / 0,4 A to external equipment.
12V and 24V power outputs with short interruption at
reset. For use of intruder detectors (PIR-detectors).
2 alarm outputs for sounders (monitored for break/short
circuit).
Alarm output (BMA), optional 24V DC and potential free
relay output.
Error output (BMF), optional 24V DC and potential free
relay output.
24V DC / 0,2A output for fire doors.
4 control outputs for zones 1-4 (transistor outputs).
Transistor output (AUX 1), activated when detec
tion zone is disabled.
Fire Alarm Control Panel BX-10
|
|